PVC / ICAT /PVC /P2TY1

Application Area

This overall screened instumentation cable is used for signal transmission in electronic control systems and panels, communication and telecom technologies, petrochemical and other commercial and industrial applications

 

Cable Construction

ConductorSolid (class 1), stranded (class 2) or fl exible (class 5) copper conductor to
BS EN 60228
InsulationPVC (EN 50290-2-21)
Core StrandingCores twisted to pairs , triples or quads in layers.
Outer Sheath ColoursBlue or Black and other colours on request
ColoursCore Colours: Colour coded in accordance to PAS 5308-1
Outer SheathPVC (EN 50290-2-22)
ScreenIndividual & Overall Al-PET foil Screens with Tinned Copper Drain Wire
Binder TapePETP foil
InsulationPVC (EN 50290-2-21)

 

Technical Characteristics

Min. Bending RadiusFixed: 8 x Cable Diameter
Operating Voltage300 V / 500 V
Test Voltage2000 V
Temperature RangeOperating -15°C to +65°C, Installation 0°C to +50°C
Flame RetardancyIEC 60332-1-2

 

Technical Tables

P2TY1 ICAT PVC / ICAT / PVC
COPPER GRADENUMBER OF PERSPRINTWEIGHT
CLASS 5 2x2x0,509.8116
5x2x0,5012.7192
10x2x0,5017.4352
15x2x0,5021.1510
20x2x0,5023.6653
CLASS 5 2x2x0,7510.5140
5x2x0,7512.7192
10x2x0,7517.4352
15x2x0,7521.2520
20x2x0,7523.8664
CLASS 2 2x2x1,512.4206
5x2x1,516.2362
10x2x1,522.4143
15x2x1,527.2997
20x2x1,530.41289
CLASS 2 2x2x2,514278
5x2x2,518.5508
10x2x2,525.6966
15x2x2,531.11410
20x2x2,5351845