XLPE / CAT / PVC P1TY1

Application Area

This invidiual and overall screened instumentation cable is used for signal transmission in electroni control systems and panels, communication and telecom technologies, petrochemical and other commercial and industrial application.

 

Cable Construction

ConductorSolid (class 1), stranded (class 2) or fl exible (class 5) copper conductor to
BS EN 60228
InsulationPE to BS EN 50290-2-23 or XLPE to BS EN 50290-2-29
Core StrandingCores twisted to pairs, triples or quads in layers
Outer Sheath ColoursBlue or Black and other colours on request
ColoursCore Colours: Colour coded in accordance to PAS 5308-1
Outer SheathPVC (EN 50290-2-22)
ScreenCollective Al-PET foil Screen with Tinned Copper Drain Wire

 

Technical Characteristics

Min. Bending RadiusFixed: 8 x Cable Diameter
Operating Voltage300 V / 500 V
Test Voltage2000 V
Temperature RangeOperating -15°C to +65°C, Installation 0°C to +50°C
Flame RetardancyIEC 60332-1-2

 

Technical Tables

P1TY1 XLPE / CAT / PVC
SectionPrintWeight
CLASS 11x20.55.435
2x20.56.252
5x20.510.4130
10x20.513.8228
15x20.516.5320
20x20.518.5410
CLASS 11x216.555
2x217.584
5x2112.7211
10x2117.2380
15x2120.77550
CLASS 21x21.57.470
2x21.58.7113
5x21.514.8290
10x21.520520
CLASS 21x22.58.295
2x22.59.81160
5x22.516.8406
CLASS 51x20.5640
2x20.56.857
5x20.511.6135
10x20.515.6234
15x20.518.8332
20x20.520.89416